Mimolite configuration parameter 8 controls the input type, either dry contact or analog (voltage)
For digital (dry contact) it needs to be set to bit =1
If your sensor does not open or short the contacts but instead supplies a voltage, the ‘analog’; configuration (Parameter 8, bit 0 = 0) may need to be set up.
The ‘digital’; configuration has a threshold around 1V while the ‘analog’; configuration can have a threshold and hysteresis within a wide range of voltages.
Refer to FortrezZ’s MIMOlite Configuration Utility for help in determining analog thresholds and configuration settings.