2441TH Temperature Calibration

2441TH Temperature Calibration

Although the temperature readings from the factory are normally accurate, if you find your thermostat is not reading the correct ambient room temperature, please follow this guide or check the user manual.

  1. Make sure the hole in the wall through which the wires are fed is properly insulated and/or the gasket is properly installed.
  2. Press and hold the Program button, tap Time/Sensor to enter Temperature Calibration Mode.
  3. Tap Mode to step between temperature calibration and humidity calibration. Temperature Calibration •  The top left number (77 in example) is the current reading according to the temperature sensor. •  The top right number (14 in example) is the current offset (represents 1.4).
  4. These numbers can change while this screen is displayed even though the primary temperature does not change. They are floating point calculations.
  5. Tap Up or Down arrows to adjust the displayed temperature to match the calibrated source. i.  Each press results in a 1° F (0.5° C) change. ii.  The calculation using example numbers below is 78 = 77 + 1.4. iii.  The offset range is from –10 to +10 actual degrees. 

Note: Use a calibrated temperature or humidity source when adjusting INSTEON Thermostat

    • Related Articles

    • Remote Temperature Control and Monitoring

      I have a cottage and want to be able to turn up the heat when I'm en-route and turn it back down when I'm not at the cottage.  Most of our Aube thermostats support a phone controller option so you can call in, enter your password and turn the heat up ...
    • Aeotec ZW100 Temperature Reporting

      By default, ZW100 reports in F and the automation controller will convert to C if necessary.
    • Average temperature reading on OMNIstat2

      The average temp function will only work when you have either 1 or 4 units, it will not work if there are 2 units or 3 units. Also this function will only work for items 23A00-1 & 23A00-2
    • Shelly Cloud Devices Control4 Drivers

      Control4 drivers are available for Shelly Cloud Gen 1 and Gen 2 / Plus devices via chowmainsoft on their web site: https://chowmain.software/drivers/control4-shelly-generic Driver Features Supports Huge Range of Shelly module functionality Native ...
    • Black Marks or Burn Marks Around or Above Aube Thermostat

      If you're seeing black marks above your Aube thermostat or any other brand, it could be due to normal operating temperature, air flow and dust coming out of the wall. However to be safe, you should get it checked by a pro to ensure the wires are ...